Waste water treatment “BIOTAL”

BIOTAL Water Treatment Plant is designed for the treatment of domestic and sewage waste waters of residential and business buildings, biologically treatable industrial waste waters of small productions, petrol stations (complex – domestic-sewage-rain waters - and car wash waters)
      Considering the specific operation features of small treatment plant, which function under conditions of high irregularity of hydraulic and organic loads and changes in the composition and properties of arriving waste waters, BIOTAL engineering solutions were mainly directed to ensuring high quality of treated waters and stable operation with reasonable capital investments and energy consumption.
      BIOTAL Water Treatment Plant involves various new patent-protected technical solutions, which allow a comprehensive solution of the problems of small water treatment facilities.
      At present over 4000 Water Treatment Plant BIOTAL are already installed in Russia, Czech Republic, Ukraine, Bulgaria, Moldova и Belarus.
      1. As a result of the treatment process, the machines make two final products, both suitable for direct end consumption:
                  -  Treated water, which can be further used;
      -  Organic-mineral fertilizer in the form of stabilized and compacted surplus active sediments;
      2. Thanks to the design of the treatment technology, no methane and hydrogen sulfide are released during operation, and that’s why there are no unpleasant smells at any stage of the waste water treatment, which allows the system to be installed in the immediate vicinity to the serviced site.
      3. The systems are completely automatic and do not require any full-time service personnel. The treatment process is controlled by controller, which allows the optimization of the operating process regarding the consumption of electric power and element operating resources; in particular, it ensures the consecutive automatic switching of the system into first, and then into second, Economy Mode of Operation, if there are no incoming waste waters after 1 and 24 hours, respectively, and into a Forced Mode of Operation – if waste water quantity is bigger than the design value. The controller display shows the actual system operation – the waste water treatment phase of the system at a certain time, the operating facilities, the Mode of Operation of the System, (Economy, Normal or Forced).
      4. There is also emergency alarm in the following cases:
                  - Electric blackout;
                  - Breakdown of any of the units;
                  - The filter bags are full with surplus active sediments;
      5. In case of an electric blackout, during the first 24 hours the system discharges the water treated earlier. Then it begins to function as a multi-level settling tank, thus ensuring that waste waters are cleaned from oils and floating dirt – the main enemies to all drainage systems. When the electric supply is restored, the system again switches into a normal mode of operation.
      6. It is possible the system can be equipped with automated complete mechanical preliminary wastewater treatment.
      7. If there are higher requirements to the quality of treated waters, the system can be equipped with a self-cleaning filter and an ultraviolet decontamination unit, and the cleaning water will be returned to the receiving chamber.
      
TECHNICAL PARAMETERS OF BIOLOGICAL SEWAGE DISPOSAL SYSTEMS “BIOTAL”
 
Index Total suspended solids                      / mg/dm3 / Biochemical oxygen demand   ( BOD5 )               / mg/dm3 O2 / Chemical oxygen demand       (COD)                   / mg/dm3 О2 /  
 
 
 
Inflow 220 390 480  
Outflow 5 – 8 5 - 7 50  
Outflow with filter 3 3 25  
Norm 35 25 125  

 
 
 
   
BIOTAL System includes six waste water treatment zones:
  1. Rough cleaning - catching rough dirt and biological pre-cleaning;
  2. Further biological cleaning - SBR Reactor level I;
  3. Further biological cleaning - SBR Reactor level II;
  4. Further biological cleaning - SBR Reactor level III;
  5. Biological filter;
  6. Tertiary settling tank.
 
Technical specifications of Biological  Sewage Disposal Systems “BIOTAL”
 
 
Type of  plant Capacity Consummated Power           /kW/ Consummated Power in economy mode 1                   /kW/ Consummated Power in economy mode 2                     /kW/ Consummated Power in economy mode  3                   /kW/ Dimensions,                     /м/
Number of  people
 
Inflow per day /м³/
BIOTAL -1.5 4 1,5 0,16 0,09 0,07 0,05 D=1,3    H=1,5
BIOTAL - 2 6 2 0,17 0,10 0,08 0,06 D=1,4    H=1,5
BIOTAL - 3 8 3 0,25 0,14 0,10 0,07 D=1,7    H=1,5
BIOTAL - 4 12 4 0,26 0,15 0,11 0,08 D=1,9    H=1,5
BIOTAL - 5 18 5 0,32 0,18 0,14 0,09 D=1,8    H=2,0
BIOTAL -10 40 10 0,90 0,47 0,32 0,25 According to the project
BIOTAL - 15 75 15 0,96 0,66 0,49 0,35 According to the project
BIOTAL - 20 100 20 1,86 1,22 0,91 0,61 According to the project
BIOTAL - 25 125 25 2,00 1,30 0.97 0,65 According to the project
BIOTAL - 30 150 30 2,15 1,38 1,03 0,69 According to the project
BIOTAL - 40 200 40 3,13 1,95 1,46 0,96 According to the project
BIOTAL - 50 250 50 3,20 2,02 1,52 1,01 According to the project
BIOTAL - 100 500 100 6,40 4,05 3,04 2,02 According to the project
BIOTAL - 200 1000 200 13,60 8,72 6,54 4,36 According to the project
BIOTAL - 500 2500 500 34,00 21,80 16,35 10,90 According to the project
BIOTAL - 1000 5000 1000 68,00 43,60 32,70 21,80 According to the project